2 - 9

CANBL_0112

TMPC Meter Stack Modules

A. Barrier

Meter socket and tenant main

breaker/wireway sections are

separated by a solid metal barrier

to guard unMetered bus against

power theft.

B. Tenant Breaker

Reliable busbar-to-busbar

connection. 200 ampere modules

accept bolt-on breakers (not Sal)

60-200 amperes. 125 ampere

modules accept 15-125 ampere

plug-on breakers.

C. Factory Phase Balanced

All Meter centres are factory phase

balanced for ease and speed of

installation.

D. Neutral Assembly

A convenient termination for neutral

conductors is in the wireway of

each module.

E. Enclosed Horizontal Bus

Added security because a non-

removable barrier exercises 800

ampere horizontal bus passing

through tenant breaker section on

5 Jaw design.

F. Equipment Ground Bar

Factory installed in side gutter, a

standard feature that’s movable to

the top or bottom gutter.

G. Continuous Ground

A convenient lay-in lug is attached

to the back of all cells. No longer do

you need to purchase ground bar

kits. Just remove knockouts and run

your ground cable from cell to cell.

H. Raintight Cap

Shipped on all TMPC Meter modules.

Enclosure type 3R rainproof.

I. Knockouts

Tangential in top and bottom,

concentric in removable

backwall plate

J. Superior Finish

Rust inhibiting phosphate primer

and grey baked enamel is standard.

All outdoor enclosures are of

galvanized steel construction

K. Meter Socket

Our unique Meter socket base is

installed without any fasteners

reducing chances for hot spots,

easily replaceable, and improves

connection to vertical bus.

L. Bus Connection

Mains and modules slip together

quickly, smoothly with front-

accessible captive bolts securing the

juncture without removing socket

interiors or bus access plate. No

additional Bus Links required.

Main bus joint bolts torque to

25 foot pounds.

M. Separate Wireway Cover

Separate covers allow easy access

to tenant breaker and wireway

section, permit work on breakers

or in wireway without disturbing

Meters or Meter covers (not shown).

N. Vertical Busbar

One-piece vertical busbar removes

most of the standard electrical

joints to the Meter socket.

Eliminating any chance of “hot

spots” from multiple connection

points.

O. Horizontal Mounting Rail

To speed up and simplify

installations, a two piece Mounting

Rail is included with each Meter

stack. Swing away feet located at

the top and bottom of structure can

be utilized for wall mounting

(not shown).

P. Padlock HASP

Included for additional security