Lug in Meter Socket Modules

Wire Size, AI/Cu

Branch Neutral

#6-2/0

125A socket module

Branch Neutral

#1/0-300 kcmil

200A socket module

Equipment Ground Bar

#14-#2

125A socket module

Equipment Ground Bar

#14-2/0

200A socket module

Optional Ground Bar (1 MMGBK)

#6-2/0

• Stacks with 1-phase horizontal bus are rated 240/120V, 1-phase, 3-wire.

Stacks with 3-phase horizontal bus are rated 208Y/120V, 3-phase, 4-wire

but can be used on 240/120V, 3-phase, 4-wire delta systems.

• All 3-phase horizontal bus modules have 4-wire, 800A cross bus and all

stacks are factory balanced for ease of installation.

• Short circuit ratings up to 100,OOOA RMS symmetrical depending upon Ale

rating of installed main tenant circuit breakers and main device.

• Lay-in Lug is attached to back of every cell. Removal of K/O allows ground

cable to run from cell to cell.

• Main tenant feeders can exit top or bottom. Knockouts are available at

all exit locations.

• Type 3R enclosure. If being used in outdoor application and exiting the top,

mount Myer type hubs on rainproof cap.

• Provision for 2-pole breaker. Plug-on type for 125A Meters and bolt-on type

for 200A Meters. Circuit breakers not included..

• Available in three and six Meter socket configuration, 5 jaw standard.

Wire Sizes: Neutral and Ground Lugs

• Each stack includes a neutral and ground bar.

• If an extra ground bar is needed order 1 MMGBK

1) Fifth jaw at 9 o’clock position included as standard.

Can be field adjusted to the 3, or 6, or 12 o’clock position.

GE Meter Centres

TMPC Residential Meter Stack Modules - 5 Jaw Design

Amperes

per

Meter

Socket

Number

of

Meter

Sockets

Bus

Ampacity

Enclosure

Type

1-Phase Horizontal Bus

(3 Horizontal Bus Bars -

A, B and Neutral)

3-Phase Horizontal Bus

(4 Horizontal Bus Bars -

A, B, C and Neutral)

Main Tenant

Breaker Type

For Specific Catalogue

Number refer to page 9

Catalogue Number Catalogue Number

125

3

Indoor &

Outdoor

-

TMPC8312R

(1)

Plug on Type

TMQRL

TMQRHL

TMQL

6

800 Indoor &

Outdoor

TMPC612

(1)

TMPC8612R

(1)

200

3

800 Indoor &

Outdoor

TMPC612R

(1)

TMPC8320R

(1)

Bolt-on Type

TMQRD

TMQ

TMQRHD

2 - 10