asecos Catalogue 2013/14 - page 304-305

GAP
-LINE
304
305
Testing of the air equipment according to EN 14175-3 (5.4.4)
Hazardous material workplace - Weighing workplace
• robust construction made of chemically resistant, anodised
aluminium profiles
• weighed materials are not scattered by the fresh air curtain
at the front
• vibration-free facility for mounting the analytical scales
on a granite block decoupled from the hazardous material
workplace
• highly effective capturing of hazardous materials inside the
workplace through special fresh air curtain technology
• prepared for connection to the on-site exhaust air system
and for electrical supply (230V/50Hz)
Standard equipment
• support frame for standing work
• workplace lighting
• extraction air monitoring with visual and audible alarm
• 2 sockets (230 V/50 Hz)
• electrical connection socket (230 V) on the roof
• empty embeded socket box including conduit for data cable
• transparent side panes made from 5 mm TSG
(tempered safety glass)
• fold-away deflector
• melamine resin coated rear wall
Technical Data
Weighing Workplace Model GAP.125.120.075.WA
with stainless steel working surface
Order No. 27461 + 27463
Model
W
x
D
x
H (mm)
Order N
o
.
GAP.125.090.075.WA, Weighing Workplace
900 x 750 x 1400
27464
n
GAP.125.120.075.WA, Weighing Workplace
1200 x 750 x 1400
27461
n
Accessories
Working surface stainless steel with cut-out for GAP.125.090.075.WA
400 x 400
27466
n
Working surface stainless steel with cut-out for GAP.125.120.075.WA
400 x 400
27463
n
Weighing workplace model
GAP.125.090.075.WA
GAP.125.120.075.WA
Outer dimensions in mm
height
1400
1400
with support frame for sitting work
2085
2085
width
900
1200
depth
750
750
Inner dimensions in mm
clear Height
1155
1155
width
865
1165
depth
650
650
Usable working surface (mm)
width
795
1095
depth
620
620
max. loading capacity (N/m
2
)
600
600
Working height (mm) mit
support frame sitting work
900
900
Weight (kg)
without support frame
96
105
support frame
19
25
total weight (kg)
115
130
point load per stilt (N)
287
325
extraction air inlet (NW/mm)
160
160
recommended exhaust air flow (m
3
/h)
431
595
approx. pressure loss (Pa)
150
285
pre-installed earthed sockets (pieces)
2
2
empty embeded socket box (pieces)
1
1
lighting (W)
36
36
Electrics (all models)
Power supply 230 V, 50 Hz, energy-saving lamp, on-off switch, light switch, monitoring electronics, supply air fan, 2 or 4 earthed sockets 230 V, 50 Hz (depending on model width).
The unit is protected with 5A fuse.
All figures are approximate values
Views GAP.125.120.075.WA
B- B
A
A
B
B
C
200 70
350
600
260
160
Abluft
EP.E.10971
Gerätedose
1400
150
2090
ca.1100
750
685
1200
EN
14175-3
(5.4.4.)
75 cm
120 cm
90cm
Hazardous Material Workplace – Weighing Workplaces
Hazardous Material Workplace – Weighing Workplaces
Ready for dispatch within
n
8–12 Weeks
Extraction air Ø160
Socket box
1...,284-285,286-287,288-289,290-291,292-293,294-295,296-297,298-299,300-301,302-303 306-307,308-309,310-311,312-313,314-315,316-317,318-319,320-321,322-323,324-325,...348
Powered by FlippingBook