Table of Contents Table of Contents
Previous Page  343 / 1070 Next Page
Information
Show Menu
Previous Page 343 / 1070 Next Page
Page Background

Credit: 405-631-9756

343

www.lockesupply.com

L

|

HVAC

COMMUNICATING SPLIT SYSTEM 16 SEER ENHANCED

AIR CONDITIONERS

4SCU16LS

208/230v Single Phase R410a Refrigerant

Dimensions

Locke# Model

A B C

L7780

4SCU16LS124P 26¾ 24¾ 29¾

L7781

4SCU16LS136P 31¼ 29

a

29¾

L7782

4SCU16LS148P 31¼ 29

a

27¾

L7783

4SCU16LS160P 31¼ 29

a

43¾

Specifications

Locke# Model# Tonnage Voltage/ Hz/

Phase

Voltage

Range

Min.

Circuit

Ampacity

Max.

Overcurrent

Device

(amps)

Compressor

Fan Motor

Refrig.

Charge

(oz.)

Weight

(lbs.)

Rated

Load

(amps)

Locked

Rotor

(amps)

Rated

Load

(amps)

Rated

HP

Nom.

RPM

L7780

4SCU16LS124P

2 208-230/60/1 216-253 13.9

20

11.4 52 1.1 1/5 1075 117 200

L7781

4SCU16LS136P

3 208-230/60/1 216-253 21.9

35

19 82 1.1 1/6 825 137 230

L7782

4SCU16LS148P

4 208-230/60/1 216-253 28.1

45

24 96 1.1 1/6 825 180 262

L7783

4SCU16LS160P

5 208-230/60/1 216-253 33.8

55

26 118 1.7 1/4 825 214 310

10 Year Limited Warranty on Compressor

5 Year Limited Warranty on all Parts

16 SEER AIR CONDITIONERS

COMPRESSOR

• High efficiency 2 stage Copeland

UltraTech™ scroll compressor

• R410a refrigerant

• Grommet mounted compressor for quiet

operation

• Internally protected against high

temperature motor overload conditions

• Heavy duty compressor sound blanket for

quiet operation

CABINET

• Full metal louvered jacket coil guard

protection

• Controls located in corner post for easy

installation and service

• Rounded corners for safety and attractive,

clean appearance

• Baked polyester paint finish over galvanized

steel for maximum durability

• PVC coated wire fan discharge grille

• External gauge ports for easy service

COIL

• Enhanced aluminum fins and copper tubing

for high efficiency and capacity

• Raised coil prevents debris from collecting

in bottom of coil and causing loss of airflow

COMPONENTS

• Full metal jacket panels remove with just

two screws per panel for easy coil cleaning

and service

• Filter drier installed for system protection

• Service valves positioned for quick

installation and easy service

• High and low pressure switches factory

installed

• Comfort Alert 2 diagnostics factory installed

• Charged for 15 ft. of line set

• Trade available components

DESIGN

• Designed for ambients up to 125°F

2 Stage

Compressor