Hybrid applications of IEC61511 – Laurie Blackmore

Equipment is categorised by type such as pressure vessels, pumps, heat exchangers etc

For each category the requirement for instrumented trips is pre-defined regardless of

level of risk

Requirements for mechanical protection such as relief valves are also defined

No performance requirements are specified

Software and systematic fault concerns are not explicitly considered

Onerous test intervals are specified. SIS transmitters every 3 months and SDV’s

annually

6

API Design Basis