Previous Page  17 / 60 Next Page
Information
Show Menu
Previous Page 17 / 60 Next Page
Page Background

the Free Field PV System utilises dc currents which do not disconnect

under fault conditions. The cost of repair as well as the economic loss

caused by downtime must be taken into account. There are also vari-

ous other factors such as the premature ageing of the PV components

and the risk of not meeting the PV plant`s contractual requirements

on the amount of power being generated.

The risk of damage caused by lightning must be determined in

accordance with the SANS/ IEC 62305 part 2 [1] where the results of

the risk analysis must be considered at the design stage. In addition

in SANS/ IEC 62305 Part 3 [1] a minimum lightning protection level III

is specified for all PV systems greater than 10 kW.

Based upon the standards it must be considered as ‘Good Prac-

tice’ to employ the proper earthing, lightning and surge protection

systems.

The installation of non-compliant / sub-standard lightning protec-

tion systems to save on the initial PV farm build costs will result in

damage and downtime of the PV system and in the medium to long

term be far more costly.

Lightning protection measures

To ensure effective protection, the Lightning Protection Systemmust

have the following optimally coordinated elements:

• Air termination and down conductor system

• Earth termination system

• Lightning equipotential bonding

• Surge protection system to power supply and data systems

These elements form the complete lightning protection system, the

parameters of each element are derived from the selected lightning

protection level which is obtained from the lightning risk assessment

process.

Figure 4: Rolling Sphere versus Protective Angle of air terminals.

Air Termination and Down Conductor System

A properly designed air termination system will prevent lightning

striking the electrical systems of the PV plant directly. All electrical

systems including the PV panels must be located within the protection

zone of the air termination system. The air termination system must

be designed in accordance with the parameters of SANS 62305 Part

3 [1] and as a minimum the air termination design should be based

upon a lightning protection level III system.

ELECTRICAL PROTECTION + SAFETY

As shown in

Figure 1

, generally the rolling sphere and angle of protec-

tionmethods are employed for an air termination system that protects

a PV array. The air termination system forms a critical part of the

external lightning protection system. In the case of an uncontrolled

lightning strike to the PV system, lightning currents will be induced

into the electrical installation and cause severe damage to the system.

Figure 5: Earth Termination System as per IEC / SANS 62305-3.

Shadowing

When designing the air termination system, care should be taken

that no solar panels are shaded by the air termination masts or rods.

Diffuse shadows caused by distant masts or rods, do not negatively

affect the PV system or their yield. Core shadows, however, cause

stress to the PV cells and this leads to bypass diodes. The required

distances from the air terminals must be calculated, for example, the

calculated minimum distance from a PV module of a 10 mm diameter

air terminal is 1,08 m.

Umbra Effect

The region of the PVmodule which is completely obscured or shaded

is called the Umbra and should be prevented in all cases. The other

region called the Penumbra or diffuse shadow, is partly obscured

since the air terminal or conductor partly covers the sun. Depending

on the dimensions of the air terminal or conductor, the minimum

distance required to prevent an umbra can be calculated.

Figure 6: Umbra Effect.

15

August ‘16

Electricity+Control