CABLE

CONDUCTORS

APPROX.

AREA

GLAND

LENGTH

mm

2

TYPE

METRES

P70017

J04

185.0 4 Core LV Board Compartment C3 (630A)

ATEX II 2 G EExed MCC 1 Incomer

ATEX II 2 G EExed

10

P70018

J04

185.0 4 Core LV Board Compartment C3 (630A)

ATEX II 2 G EExed MCC 1 Incomer

ATEX II 2 G EExed

10

P70019

J04

185.0 4 Core LV Board Compartment C4 (630A)

ATEX II 2 G EExed MCC 2 Incomer

ATEX II 2 G EExed

10

P70020

J04

185.0 4 Core LV Board Compartment C4 (630A)

ATEX II 2 G EExed MCC 2 Incomer

ATEX II 2 G EExed

10

E70021

J01

95.0 1 Core LV Board Earth Bar

ATEX II 2 G EExed MCC1 Earth Bar

ATEX II 2 G EExed

10

Green/Yellow Outer Sheath

E70022

J01

95.0 1 Core LV Board Earth Bar

ATEX II 2 G EExed MCC2 Earth Bar

ATEX II 2 G EExed

10

Green/Yellow Outer Sheath

C70023

J02

1.5

2 Core Crash Stop Node

ATEX II 2 G EExed MCC 1 Crash Stop Compartment

ATEX II 2 G EExed

30

C70024

J02

1.5

2 Core Crash Stop Node

ATEX II 2 G EExed MCC 2 Crash Stop Compartment

ATEX II 2 G EExed

30

70025

Spare - Issued by SW

70026

Spare - Issued by SW

70027

Spare - Issued by SW

70028

Spare - Issued by SW

70029

Spare - Issued by SW

120

REV DATE BY DRN

CHK'D

APP'D

DESCRIPTION

PLANT

A 22.02.13 MM MM PJP PJP MM MM Issued For Construction

TITLE

B 25.02.13 MM MM PP

MM

Cables C70023 & C70024

SHEET 1 OF 1

CLIENT DRG No

REF No. SI451002_SCH

Cables in Parallel

Future Cables

TOTAL

NOTES:

IF NOT SIGNED THIS DOCUMENT IS UNCONTROLLED

1) Refer to P&I Design Cable Specifications for details on Cable Type.

Immingham Storage Co. - East Terminal

No. 7 Switchroom - Cable Schedule

Denotes Cable Modified

Denotes Cable Deleted

Cables in Parallel

Denotes Cable Added

INSTRUMENT/ELECTRICAL CABLE SCHEDULE

CABLE ROUTE

REMARKS

REFERENCE TYPE

No.

FROM

TO

GLAND

TYPE