CABLE
CONDUCTORS
APPROX.
AREA
GLAND
LENGTH
mm
2
TYPE
METRES
P70017
J04
185.0 4 Core LV Board Compartment C3 (630A)
ATEX II 2 G EExed MCC 1 Incomer
ATEX II 2 G EExed
10
P70018
J04
185.0 4 Core LV Board Compartment C3 (630A)
ATEX II 2 G EExed MCC 1 Incomer
ATEX II 2 G EExed
10
P70019
J04
185.0 4 Core LV Board Compartment C4 (630A)
ATEX II 2 G EExed MCC 2 Incomer
ATEX II 2 G EExed
10
P70020
J04
185.0 4 Core LV Board Compartment C4 (630A)
ATEX II 2 G EExed MCC 2 Incomer
ATEX II 2 G EExed
10
E70021
J01
95.0 1 Core LV Board Earth Bar
ATEX II 2 G EExed MCC1 Earth Bar
ATEX II 2 G EExed
10
Green/Yellow Outer Sheath
E70022
J01
95.0 1 Core LV Board Earth Bar
ATEX II 2 G EExed MCC2 Earth Bar
ATEX II 2 G EExed
10
Green/Yellow Outer Sheath
C70023
J02
1.5
2 Core Crash Stop Node
ATEX II 2 G EExed MCC 1 Crash Stop Compartment
ATEX II 2 G EExed
30
C70024
J02
1.5
2 Core Crash Stop Node
ATEX II 2 G EExed MCC 2 Crash Stop Compartment
ATEX II 2 G EExed
30
70025
Spare - Issued by SW
70026
Spare - Issued by SW
70027
Spare - Issued by SW
70028
Spare - Issued by SW
70029
Spare - Issued by SW
120
REV DATE BY DRN
CHK'D
APP'D
DESCRIPTION
PLANT
A 22.02.13 MM MM PJP PJP MM MM Issued For Construction
TITLE
B 25.02.13 MM MM PP
MM
Cables C70023 & C70024
SHEET 1 OF 1
CLIENT DRG No
REF No. SI451002_SCH
Cables in Parallel
Future Cables
TOTAL
NOTES:
IF NOT SIGNED THIS DOCUMENT IS UNCONTROLLED
1) Refer to P&I Design Cable Specifications for details on Cable Type.
Immingham Storage Co. - East Terminal
No. 7 Switchroom - Cable Schedule
Denotes Cable Modified
Denotes Cable Deleted
Cables in Parallel
Denotes Cable Added
INSTRUMENT/ELECTRICAL CABLE SCHEDULE
CABLE ROUTE
REMARKS
REFERENCE TYPE
No.
FROM
TO
GLAND
TYPE