No.3 Pumphouse Modifications – MCC - Basis of Design

P & I Design Ltd

DOCUMENT NO: SI451003_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: A DATE: 07.08.12

Tel: + 44 (0)1642 617444

PAGE 4 OF 7

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

Controls Voltage 24Vdc. A central control transformer will be provided in each MCC

and 24Vdc individually fused and distributed from here to each drive

compartment

Short Circuit

Protection

It is noted that the site preference is to use MCCBs. The circuit

currently shows fuse protection. Calculations will have to be

performed prior to construction issue drawings being issued to verify

earth fault clearance times are satisfied using MCCBs with the cables

currently installed.

The MCC circuit design is generic. Any interfacing with a control system, for example

with a road loading batching system, will be dealt with in a logic panel co-located in the

same switchroom. This is likely to culminate in a single permissive contact wired from the

logic panel to the MCC compartment. This design enables the MCC circuit design to

always be the same and thus familiar to the user.

A marshalling section will be provided, thus all field control wiring will be diverted to the

marshalling section from where it will be internally wired through the MCC. This again

permits a standard circuit design to be utilised.

3.2

MCC Operator Interface

Compartment door mounted controls :-

o

Start (momentary pushbutton)

o

Stop (Red mushroom head stayput pushbutton)

o

Auto / Off / Manual control mode selector switch

Compartment door mounted lamps for :-

o

Running (Green)

o

Stopped (Red)

o

Fault (Amber) : Fault = Soft Start Fault, Overload or Field mounted stop

button pressed

o

Low Suction Level (Amber)

o

High Discharge Temperature (Amber)

Door mounted overload reset button

o

Soft Start – via door mounted operator panel

o

DOL – via door mounted button

Power Indication

o

Drives ≥ 37kW to have multi-function power meter. Meter to have the

ability for Modbus output for connection if desired to PLC/SCADA for

remote monitoring, trending and reporting

o

Drives < 37kW to have door mounted ammeter

o

All the above to be via current transformers

Compartment door fan and filtered inlet for all soft start drives