Transformers + Substations Handbook: 2014

Noteworthy is the fact that the TP-1 (Energy Star) efficiency, cop-

per-wound unit, loaded at 75% of its nameplate capacity (column 7),

saves over US $88 (ZAR 867) a year compared with an aluminium-wound

TP-1 model (column 6), but costs only US $85 (ZAR 837) more initially.

At only 50% loading, the copper TP-1 unit (column 11) saves about US

$50 (ZAR 492) a year compared with the same aluminium unit (column

10). No-load loss is reduced from 350 to 320 watts because the great-

er conductivity of copper windings allows a smaller core to be used,

so energy continues to be saved, even at light loading levels.

For greater savings, the premium efficiency, copper-wound unit

saves over US $401 (ZAR 3 952) a year at 75% loading (column 8),

compared with the aluminium TP-1 model (column 6), and only costs

an additional US $1 235 (ZAR 12 172).

Minimising owning cost

Whenever possible, compare competing transformer models by asking

for the load and no-load losses in watts and look at the total cost of

ownership. Given their life span, buying a unit based only on its initial

cost is uneconomical and foolish.

Transformer life cycle cost takes into account the initial transform-

er cost and also the cost to operate and maintain the transformer over

its life. This requires that the Total Owning Cost (TOC) be calculated

over the life span of the transformer. With this method, it is possible

to calculate the real economic choice between competing models.

A basic version of the TOC formula would be:

TOC = initial cost of

transformer + cost of the no-load losses + cost of the load losses

No-load losses are constant whenever the transformer is energised.

Specifying copper windings can minimise both the load loss and the

no-load loss, by allowing for a smaller core. If the load is known or can

be predicted, choose a transformer that will be loaded to about 75%

of its nameplate rating. Oversizing the unit increases the no-load loss-

es, as well as the purchase price, unnecessarily.

If the actual losses in watts are not available, and you are seeking

the transformer with the lowest losses, choose a transformer with

80°C rise, with M6 steel grade core or better, and copper windings.

Conclusion

Transformers remain a fundamental part of electrical distribution sys-

tems. The correct sizing for the load they are expected to carry and the

material used in their internal windings can dramatically impact their

life time and cost. It is worth reiterating that the recommended loading

for economic sizing of a transformer is typically around 75% of name-

plate and a premium efficiency, copper-wound, unit will result in sig-

nificant savings in the long run.

Reference

[1] NEMA TP 1: 2002. Guide for determining energy efficiency for

distribution transformers.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

StdAl

TP-1

Al

TP-1

Cu

Prem

Cu

Std

Al

TP-1

Al

TP-1

Cu

Prem

Cu

Std

Al

TP-1

Al

TP-1

Cu

Prem

Cu

Std

Al

TP-1

Al

TP-1

Cu

Prem

Cu

% of name

plate load

100

100

100

100

75

75

75

75

50

50

50

50

35

35

35

35

Core

loss (W)

375

350

320

190

375

350

320

190

375

350

320

190

375

350

320

190

Conductor

loss

2829 1874 1670

993

1591

1054

940

559

707

469

418

248

1591

176

157

113

Total

loss (W)

3204 2224 1990 1183 1966

1404

1260

749

1082

819

738

438

1966

526

477

303

Efficiency

loss (%)

95.9 97.12 97.42 98.45 96.62 97.56

98.69 97.19 97.86 98.07 98.84 96.62 98.04 98.04 98.86

Transformer

cost ($)

1366

(R13463)

1979

(R19505)

2064

(R20343)

3214

(R31678)

1336

(R13463)

1979

(R19505)

2064

(R20343)

3214

(R31678)

1336

(R13463)

1979

(R19505)

2064

(R20343)

3214

(R31678)

1336

(R13463)

1979

(R19505)

2064

(R20343)

3214

(R31678)

Comparison:

Additional

cost

compared

with standard

unit ($)

643

(R6337)

728

(R7175)

1878

(R18510)

643

(R6337)

728

(R7175)

1878

(R18510)

643

(R6337)

728

(R7175)

1878

(R18510)

643

(R6337)

728

(R7175)

1878

(R18510)

Energy cost/

year ($)

1964

(R19364)

1363

(R13441)

1220

(R12030)

725

(R7149)

1205

(R11882)

8 60

(R848561)

772

(R7615)

459

(R4526)

663

(R6539)

502

(R4949)

452

(R4460)

268

(R2647)

1205

(R11882)

322

(R3179)

292

(R2882)

185

(R1831)

Annual

energy

cost saving

compared

with standard

unit ($)

600

(R5923)

744

(R7337)

1239

(R12214)

344

(R3396)

432

(R4267)

746

(R7355)

161

(R1589)

210

(R2079)

394

(R3448)

69

(R688)

99

(R985)

206

(2036)

Payback

period (years)

1.07

0.98

1.52

1.87

1.68

2.52

3.99 3.45

4.76

9.20

7.29

9.09

Table 1 - courtesy: Olsun Electrics, Richmond, IL.

• Al (Aluminium)

• Cu (Copper)

• Std (Standard)

• Prem (Premium)

Notes:

• Standard and AluminiumTP-1 units are 150°C rise, CopperTP 1 unit is 115°C rise,

Premium unit is 80°C rise.

• Loss values at 100%, 75% and 50% nameplate load are at reference temperature

• Loss values at 35% nameplate load are at 75°C in accordance withTP-1

• Energy cost assumed to be $0,07/kWh

• Conversions from US$ to ZAR - 18 July 2013

Table 1: Payback time comparison for 75 kVA dry-type transformers.