13
Chemical Technology • July 2015
and emergency plans. As mentioned earlier, it is common
to initially specify an SIS with modern technology. This
usually comprises a sensor to measure a variable, a logic
solver to manipulate the signal from the sensor, a converter
to change the signal into a usable form (often a solenoid
valve which changes an electric signal to a pneumatic or
hydraulic signal) and a final shut-off element (usually an
actuated valve or a power cylinder).
SISs can be designed and built with safety integrity to
comply with any of the specified SILs. Typically, a SIL1 would
be built as a single channel system with a single sensor,
a single logic solver stage and a single actuated valve as
shown in Figure 4. This configuration is referred to as a 1
out of 1 system, denoted 1oo1. Each of the three parts of
the SIS are called sub systems and all three subsystems
must satisfy SIL 1 requirements both separately and when
combined.
A SIL2 would typically be achieved by providing redun-
dancy as a dual channel shown for the sensors and actua-
tors in Figure 5. Here only one out of the 2 channels needs
to function for the SIS to function, ie, one channel can fail.
This configuration is referred to as a 1 out of 2 system,
denoted 1oo2.
A SIL3 may sometimes need to be built with 3 channels
as shown for the sensors in Figure 6. Here only one chan-
nel out of 3 needs to function for the SIS to function, ie, 2
channels can fail. This configuration is referred to as a 1 out
of 3 system, denoted 1oo3. Note that in extreme situations,
3 channels of solenoid valves and shut off valves could
also be used, but the reliability of two solenoid valve-shut
off valve combinations is usually high enough to obviate
the use of three.
Also, a SIL 3 usually requires a 1oo2 arrangement for
logic solvers as well as actuators. However some high
performance logic solvers can achieve SIL3 in a 1oo1 con-
figuration due to their ability to detect virtually all dangerous
failures and shutdown the process automatically.
A SIL4 would be very reliable, but also very expensive,
whereas a SIL 1 would be cheaper but less reliable, ie, of
lower integrity.
Protection system integrity
Consider a simple shut down system comprising a sensor,
logic solver solenoid valve and shut off valve. In the above
example this could be the high level trip. Assuming, as an
illustration, that each component (sub system) has a failure
rate of 0,1 per year, ie, it fails once in ten years, then the
total failure rate of the string (3 sub-systems in series) is
f = 0,1 + 0,1 + 0,1 + 0,1 = 0,4/year.
If the system is rarely or never tested, the probability
of failure on demand PFD increases with time and would
become very high. However, if tested every six months, one
could say that on average it would be in a fail state half
the test time. This is so because, say we divide the time
between tests T in 10, then if it fails after 0,1T it would be
in a fail state (1 - 0,1)T, if it failed after 0,2T it would be in
a fail state (1 - 0,2)T and continuing if it failed after 0,9T, it
would be in a fail state (1 - 0,9)T. Adding all ten failed times
and taking the average of the failed times is equal to 1/2T.
Thus in the example, if tested every six months, the av-
erage failed time is 6 months/2 = 3 months equal to 0,25
year. But the failure rate of the protection string f is 0,4 /
year, so the PFD = ½ * f * T = 0,4*0,25 = 0,1 or 10%. The
PFD can be reduced by testing more frequently. If tested
every three months, the PFD = ½ * 0,4 *3/12 = 0,05. This
meets the requirement of a SIL1.
The above result is not totally realistic because of ig-
noring common cause failures of the components due to
factors such as electrical interference, excessive vibration
or excessive temperatures, etc. This typically restricts the
PFD reduction to about 10 % of the 1oo1 PFD.
PFD can also be reduced by incorporating redundancy,
as mentioned earlier, into subsystems, eg, the level sensing.
Thus using 1oo2 or 1oo3 systems together with automatic
diagnostic fault detection, the PFD can be further reduced
to allow a SIL 2 and SIL 3 to be achieved. Such methods
can be applied to any of the sub systems and are generally
used to improve the performance of the weakest part of
the ‘string’. Typically 1oo2 is widely used and sometimes
1oo3 is justified.
Although a 1oo3 SIS is highly reliable, it is also vulnerable
Figure 3: Adding independent layers of protection
PLANT MAINTENANCE, SAFETY,
HEALTH & QUALITY




