Chemical Technology • July 2015
14
for spurious activation. The disadvantage is that the installa-
tion would be unnecessarily shut down, incurring production
costs. This problem can be overcome by a voting system,
eg, a 2oo3. In this configuration, two channels must initiate
activation before the SIS will function. Therefore, if one faulty
channel initiates activation that would unnecessarily shut
down the process, the logic solver would disable the shut
down as it will have been set up to only enable shutdown
if there are two activation signals. However, 2oo3 voting
increases the PFD by a moderate amount.
Note also, that achievement of SIL 1,2, 3 or 4 depends
equally on the measures taken to ensure systematic safety
integrity has been achieved. Hence SIL performance cannot
be claimed for an SIS unless the design and maintenance
specifications have been done in accordance with the
requirements of the internationally recognized standards
such as IEC 61508 or IEC 61511.
Incorporating other layers of protection
LOPA allows one to take credit for other layers of protection
which may then allow one to reduce the required SIL rating
of the SIS, thereby reducing the cost as well as ensuring
that the system is not overprotected.
In the example, the operator failure is the initiating
event, with an initiating event frequency IEF, the high level
trip LSH of the feed is the SIS, so with LOPA one could take
credit for the control system assuming it has a PFD = 0,1.
Therefore the mitigated risk R, excluding the SIS, but with
other IPL included is:
R = Initiating event frequency * Product of the PFD’s of
all IPLs
= IEF * [ PFD( IPL
1
) * …PFD(IPL
n
) ] = 1 * 0,1 = 0,1 / y
Revised risk reduction factor RRF=
=
= 0,1/ 0,001 = 100 which is now much lower.
Hence the required PFD of the SIS (high level trip) can
be reduced to PFD = 1/100 = 0,01 = 1 * 10
-2
.
Referring to Table 2 on page 12, this value falls between
10
-2
up to 10
–1
which means that a lower SIL 1 can be
specified for the SIS which is the high level trip.
Risk graph method
A simple short-cut method according to IEC 61508/61511
is using the risk graph shown in Figure 7 on page 15.
Inputs into the risk graph are as per the Figure 8 below.
In the example, if we assume a consequence ‘Perma-
nent injury > 1 person, 1 death’≡ C2, exposure time is
‘Frequent to permanent’≡ F2, avoidance of the hazard is
‘Almost impossible’≡ P2 and the probability of an unwanted
occurrence is ‘Slight’≡ W2. Then, following through the risk
graph, one arrives at a SIL 2.
If credit is taken for the control loop acting to reduce
the probability (W2 reduces to W1) of the event, then this
would be one layer of protection and the required rating
of the SIS will then reduce to SIL 2 – 1SIL = SIL1. Note: a
control loop would not normally be rated SIL 1 or be called
an SIS without expensive features. However, it is reasonable
to claim that the control loop reduces the probability of the
event by a factor of 10 (ie, PFD = 0,1).
SIL matrix method
A SIL matrix may be drawn up as shown in Table 3 opposite,
to simplify the SIL rating of Safety Instrumented Systems.
Therefore, having estimated the likelihood of the initiating
event of a hazard and knowing the severity, onemay read off
the required initial SIL level directly. Incorporating additional
layers of protection, the SIL is decreased by 1.
In the example above of filling a tank, the initiating event
is 1/year for medium environmental damage, a SIL 2 is
indicated. Incorporating a layer of protection, moving one
column to the right, shows a SIL1.
Note: ‘ALARP’ ≡ ‘As Low As Reasonably Practical’, means
the design can be accepted, no further risk reduction is
necessary, provided it can be shown that this will not be
practical or cost-effective.
Conclusions
Simple explanations have been given to illustrate layers of
protection. It was pointed out that such layers of protec-
tion must have sufficient integrity to prevent initiation or
propagation of a hazardous event. The suitability of layers of
protection must be assessed against targets of tolerability,
drawn up by the owner or organisation of the installation.
Safety instrumented systems are normally incorporated
in hazardous installations as a first choice of a layer of pro-
tection. The required integrity of such a layer of protection
is expressed as a probability of failure on demand, and
Mitigated risk R
Target frequency TF
Figure 4: SIL 1 instrumented protection configuration
Figure 5: SIL 2 instrumented protection configuration




