Local Fuel plc - Shoreham Oil Terminal
Safety Instrument System Functional Safety Assessment Stage 5
P & I Design Ltd
DOCUMENT NO: LF364100_RPT
2 Reed Street, Thornaby, UK, TS17 7AF
ISSUE: B DATE: 07.06.2016
Tel: + 44 (0)1642 617444
PAGE 31 OF 51
Fax: + 44 (0)1642 616447
www.pidesign.co.ukdetailing the intended operation of all tanks in respect to the SIS would enhance the
understanding of the proposed system, in relationship to Local Fuel requirements.
Action 13:
5.7.2 Performance
The FSA reviewed the performance of the SIS over the 18 months that it has been in the
ownership of Local Fuel, the following were considered:
Actual Activations: (Demand on System)
No activations have occurred.
Spurious Trips:
No spurious trips have occurred.
Random Hardware Failure:
No hardware failures have occurred.
Systematic Capability and Systematic Failures:
No systematic failures have been identified.
Operating Difficulties:
Local Fuel plc have taken over the operation of the Terminal and the SIS with no handover
from Valero. They have now operated the system for 18 months and have had no difficulty or
problems with the system.
Interface with BPCS:
The import valve is opened and closed via the HMI system. However, the BPCS can not
interfere with the operation of the SIS system as this is performed on the dedicated hardwired
input to the valve.