Table of Contents Table of Contents
Previous Page  23 / 349 Next Page
Information
Show Menu
Previous Page 23 / 349 Next Page
Page Background

P & I Design Ltd.

Instrument Specification

CLIENT:

REV DATE

BY

CHKD

APPD

CLIENT REF.

Simon Storage (Immingham East)

A 10/03/99 AJH DRR

DRR

FINA Rail Loading

B 06/04/99 AJH DRR

DRR

P & I REF.

SI039004.SPC

SHT

1

OF

2

ITEM:

Electrical

Component

GENERAL

Tag Number

N/A

B

Service

FINA DERV Rail Loading Operator Control Panel

Area Classification

Zone 1 IIB T3

UNIT

Type

Control Unit c/w terminals, indicator

lamps and switches.

Supply

24VDC

Case

Manufacturers Standard

Connections

Terminals

Mounting

Surface

Enclosure Class

IP66

Electrical Classification

EEx de IIC T6

OUTPUT

B

Type

Box to include 26 off SAK2.5 EEx’e’ terminals and

the following EEx’de’ controls:-

1 x Mushroom head stay-put-stop pushbutton 1N/O

& 1N/C contact

1 x 2-position selector switch, 1N/O contact in each

position.

3 x Momentary Pushbuttons 1N/O & 1N/C contact

B

5 x Lamps, 24VDC (Red)

1 x Lamp, 24VDC (Green)

B

1 x Lamp, 24VDC (Amber)

Enclosure to be drilled for the following gland

entries:-

1 x 25mm (bottom)

OPTIONS

For

internal,external layout & label details see

drawing SI039020.

MANUFACTURERS

Supplier

CEAG

DATA

Model Number

1 off GHG448 with built in components

DOCUMENTATION

See attached Documentation Specification

ZZ#-ECA1.SPC

Documentation Requirement