Table of Contents Table of Contents
Previous Page  40 / 349 Next Page
Information
Show Menu
Previous Page 40 / 349 Next Page
Page Background

P & I Design Ltd.

Instrument Specification

CLIENT:

REV DATE

BY

CHKD

APPD

CLIENT REF.

Simon Storage (Immingham East)

A 09.04.99 AJH DRR

DRR

FINA Rail Loading

P & I REF.

SI039012.SPC

SHT

1

OF

2

ITEM:

Multiplexer System

(Digital)

GENERAL

Tag Number

N/A

Service

North & South Siding MUX

Area Classification

Zone 1 IIB T3

RECEIVER

Supply

24Vdc

No. of Channels

16

Contact Outputs :

Type

Relay (Energised when input ‘closed’)

Rating

240V, 1A, 120VA, ac: 50V, 0.1A, 5W, dc.

Indication Outputs : Type

LED x 16

Fault Outputs :

Type

MUX (LED & Relay), Highway (Relay)

Housing : Material

Moulded Polycarbonate

Enclosure Class

General Purpose

Electrical Classification Safe Area

Electrical Connection Terminals

Mounting

DIN Rail

TRANSMITTER

Supply

Loop powered Via MTL 3052 Isolator

No. of Channels

16

Field Inputs :

Type

Contact Inputs

Rating

‘Closed’ if > 2.1 mA, ‘Open’ if < 1.2mA

Operating Range

0.5km typically

Housing : Material

Moulded Polycarbonate

Enclosure Class

IP67

Electrical Classification EExia IIC T6

Electrical Connection Terminals

Mounting

DIN Rail

OPTIONS

MANUFACTURERS

Supplier

MTL

DATA

Model Number

4 off Reciever: MTL825B

4 off Transmitter: MTL821B

4 off Isolator: MTL3052

DOCUMENTATION

See attached Documentation Specification

ZXS-MXA1.SPC