Page Background

P & I Design Ltd.

Instrument Specification

CLIENT:

REV DATE

BY

CHKD

APPD

CLIENT REF.

Simon Storage (Immingham East)

A 15/04/99 AJH DRR

DRR

FINA Rail Loading

P & I REF.

SI039017.SPC

SHT

1

OF

3

ITEM:

Electrical

Component

GENERAL

Tag Number

N/A

Service

See Sheet 2

Area Classification

Zone 1 IIB T3

UNIT

Type

Sheet Steel Enclosure

Supply

240VAC & 24Vdc comms

Case

Zinc sprayed (6mm gland plates)

Connections

See OPTIONS

Mounting

Surface

Enclosure Class

IP66

Electrical Classification

EEx’e’ & ‘i’

OUTPUT

Type

24Vdc

OPTIONS

Enclosure to be supplied with:-

1.

2 off SAK2.5 EEx’e’ terminals

2.

1 off EK2.5 EEx’e’ terminals

3.

1 off screen earth bar, with 25 ZB4 earth

clamps.

Enclosure to be drilled & tapped for the following:-

1. 18 off 20mm entries (bottom)

2. 4 off 20mm entries, 2 plugged (top)

MANUFACTURERS

Supplier

J HEMY SYSTEMS

DATA

Model Number

2 off KLIPPON TB12EX

DOCUMENTATION

See attached Documentation Specification

ZZ#-ECA1.SPC

TAG No.

SERVICE

RANGE

COMMENTS