Immingham Storage Co Ltd – Immingham East Terminal
IME-SIS1 - Safety Instrument System Safety Requirement Specification
P & I Design Ltd
DOCUMENT NO: SI277010_RPT
2 Reed Street, Thornaby, UK, TS17 7AF
ISSUE: G DATE: 31.10.14
Tel: + 44 (0)1642 617444
PAGE 7 OF 13
Fax: + 44 (0)1642 616447
www.pidesign.co.uk2.3
System Structure
2.3.1 System Model – No. 4 East Tanks
Tanks 561, 564 & 568.
The SIF is based upon a 1oo1 (single) sensor, 1oo1 (single) logic solver and 1oo1 final
element with no redundancy.
Note 1: Shaded areas do not affect safety function
Note 2: New System models will be developed for future phases of the SIS
Level
Element
Sensor Subsystem
Logic Subsystem
Safety Relay
With Manual
Reset
Solenoid
Valve
Final Element Subsystem
BPCS
Fault Trip SIS Valve
Status Status Status
Feedback
Relay
Air Isolation
Actuated
Valve
Valve
Limit
Switches
Level
Switch