Local Fuel – Shoreham Oil Terminal

Safety Requirement Specification

P & I Design Ltd

DOCUMENT NO: LF364005_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE:C DATE: 14.08.15

Tel: + 44 (0)1642 617444

PAGE 7 OF 19

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

2.3.2 Import to Distillate and Additive Tanks

The Safety Instrumented system will include high high level switch elements on the distillate

and additive tanks although no automated final elements will be installed.

On detection of any storage tank high high level, fault or power supply failure, the output is

removed to the relay, resulting in the annunciator for that tank illuminating. Manual

intervention would be required.

The additive tanks are not in service and the level sensors associated with these tanks have

been linked out.

The system will also shut down flow to the gasoline tanks in the event of a high level in the

Marine Gas oil tanks (Tanks 2 & 4).