Local Fuel – Shoreham Oil Terminal

Safety Requirement Specification

P & I Design Ltd

DOCUMENT NO: LF364005_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE:C DATE: 14.08.15

Tel: + 44 (0)1642 617444

PAGE 13 OF 19

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

4

FUNCTIONAL REQUIREMENTS

See SIS Overview Trip Matrix, LF364001_SCH

4.1

SIS Inputs

1.

Tank Level Switch Elements

a.

Tank 1 – LE1

b.

Tank 2 – LE2

c.

Tank 3 – LE3

d.

Tank 4 – LE4

e.

Tank 5 – LE5

f.

Tank 6 – LE6

g.

Tank 7 – LE7

h.

Tank 8 – LE8

i.

Tank 9 – LE9

j.

Tank 10 – LE10

2.

Manual Reset Pushbutton/Remote Input

a.

East Bund common reset relays operated by a panel pushbutton or remote

input :– Reference Drawing LF364020

At present only 2 gasoline tanks are in service, tanks 1 & 3. However the system is designed

for tanks 1, 2, 3 & 4 to shut the gasoline pipeline valve on activation of level switch in any of

tanks 1 to 4.

4.2

SIS Logic Solvers

1.

Safety Relay with feedback verification before reset.

a.

R088

b.

R252

c.

R292

d.

R332

e.

R492

f.

R532

g.

R572

h.

R612

i.

R652

j.

R692

4.3

SIS Outputs

1.

Ball valve with fail closed, electro hydraulic, spring return actuator.

a.

Pipeline Import Valve

XV162