Safety IntelliPoint RF, SXRNTXX Series User's Manual

12

2.5.7 Re-Calibration

Do not push the "ReCal"

Button without first

ensuring the material being measured is below

the sensing element.

If system is powered on the bench prior to installation, or moved

from one tank to another, Re-Calibration is necessary to allow

software to capture the air capacitance generated by sensing

element in the tank.

Merely press and hold the "ReCal" Button for 5 seconds (

Shown

in Figure 2-4

). Green LED flashes for 60 seconds before reset

occurs.

[

Remove power from the system while the green LED is flashing

and reset will occur immediately

].

The system is now ready for installation.

Nonvolatile Memory

The IntelliPoint has nonvolatile memory which allows the unit

to re-start after power outages without recalibrating.

When The IntelliPoint is powered for the first time the internal

microprocessor records and stores the “Air” value.

This is the uncovered value of the sensor mounted in the vessel.

The IntelliPoint will also store the last covered value and the

last uncovered value.

Whenever The IntelliPoint is powered it uses these values as

a reference point to determine its current condition (normal or

alarm).

The IntelliPoint has nonvolatile memory which retains the

recorded values even if power is lost for months. When

The IntelliPoint regains power after a power outage, the

microprocessor compares the stored values to the current

measured value. It will then determine its current status

based on this.

Example:

Air value is 10pF

covered value is 20pF

Uncovered value is 11pF

Setpoint = Alarm or recovery value.