Any initial conditions which must be satisfied prior to undertaking the test.

Adequate cross references to any other documents, manuals etc.

Clear and concise procedural steps which adequately define the tasks necessary to

perform the test safely and efficiently.

Proof test procedures should be designed in order to detect dangerous undetected failures by,

where possible, providing realistic end to end testing. Where full testing cannot be conducted,

partial testing will be utilised, but the testing plan will identify when a full test is required to

ensure the PFD of the component and system is not compromised.

Any warnings or specific issues that should be drawn to the attention of the tester should be

clearly and conspicuously stated.

The FSM will schedule the inspection, maintenance and test routines utilising the site

competent personnel or an organisation to carry out the inspection, maintenance and test

routines.

Full documentation of the findings of every inspection, maintenance and test routine,

including any failures or faults will be produced by, or on behalf of Local Fuel plc. The

documentation associated with proof testing and inspection should a minimum contain:

SIF tag number.

Inspection, maintenance and test procedure tag number.

Brief description of inspection, maintenance and test.

Date carried out.

Name/s of person/s carrying out inspection, maintenance and test routine.

Results of inspection and test routine including “as found” and “as left” condition.

Any critical steps which following the tests may leave the system in-operable.

o

If critical steps are identified then independent checks of that task should be

identified and recorded on the test procedure.

Any reports of overdue tests, demands upon the SIF, or spurious operation and failures during

operation or under test, shall be investigated and documented by the FSM.

Periodically the FSM shall ensure that a review of the data from demands, mean time to

restore, spurious trips and testing is performed to verify that assumptions made during the SIL

Determination and design activities were accurate and complete.

Local Fuel plc ensure that terminal operating personnel understand what is required of them

in the case of activation of the SIS. The FSM will ensure that operators log and record all SIS

activities, such as activations, spurious events and failures using a dedicated SIS failures

report.

The FSM will review each and every report to ensure Functional Safety is maintained.

All terminal operations and procedures are conducted utilising Standard Operating Procedures

(SOP’s) to which operators are trained and competent in carrying out.