Table of Contents Table of Contents
Previous Page  148 / 2440 Next Page
Information
Show Menu
Previous Page 148 / 2440 Next Page
Page Background

Edition 47 4-13

Engines

4

Cat Generator Sets

Diesel Ratings

60 Hz

Model

rpm

Standby

Prime

ekW

3-Phase Output*

D40

1800

40

36

D50

1800

50

45

D60

1800

60

55

D80

1800

80

72

D100

1800

100

90

D125

1800

125

114

D150

1800

150

136

D175

1800

175

158

D200

1800

200

Single Phase Output**

D40S

1800

40

36

D50S

1800

50

45

D60S

1800

60

55

D80S

1800

80

72

D100S

1800

100

90

*

*All ratings at 0.8 pf.

**All ratings at 1.0 pf.

60 Hz

Standby

Prime Continuous

Model

ekW

1800 rpm

C9

200

180

C9

250

225

C9

300

275

3406C

300

275

C15

350

320

C13

350

320

C13

400

350

C15

400

365

C15

450

410

C15

500

455

C18

550

500

C18

600

545

3412C

650

591

3412C

700

635

C27

750

680

3412C

750

680

C27

800

725

3412C

800

725

C32

1000

910

830

3512

1100

1000

890

3512

1250

1135

1010

3512B

1400

1275

3512B

1500

1360

1230

3512C

1500

1360

1230

3516

1750

1600

1450

3516B

2000

1825

1640

3516C

2000

1825

1650

3516B

2250

3516C-HD

2500

2250

2050

C175-16

3000

2725

2500

C175-16

3100

2825

2600

C175-20

4000

3600

3250

Cat Generator Sets

Diesel Ratings

Rating Definitions:

Standby Power Rating

— Output available with varying load for

the duration of the interruption of the normal source power.

Average power output is 70% of the standby power rating.Typical

operation is 200 hours per year, with maximum expected usage

of 500 hours per year.

Prime Power Rating

— Output available with varying load for an

unlimited time. Average power output is 70% of the prime power

rating.Typical peak demand is 100% of prime rated ekW with 10%

overload capability for emergency use for a maximum of 1 hour

in 12. Overload operation cannot exceed 25 hours per year.

Continuous Power Rating

— Output available with non-varying

load for an unlimited time. Average power output is 70-100% of

the continuous power rating. Typical peak demand is 100% of

continuous rated ekW for 100% of operating hours.

Applicable Codes and Standards: AS1359, CSAC22.2 No100-04,

UL142, UL489, UL869, UL2200, NFPA37, NFPA70, NFPA99, NFPA110,

IBC, IEC60034-1, ISO 3046, ISO 8528, NEMAMG 1-22, NEMAMG 1-33,

2006/95/ECforLowVoltage,2006/42/ECforMachinery,2004/108/EC.

Fuel rates

are based on fuel oil of 35° API [16° C

(60° F)

] gravity

having an LHV of 42 780 kJ/kg

(18,390 Btu/lb)

when used at 29° C

(85° F)

and weighing 838.9 g/liter

(7.001 lb/U.S. gal)

. Additional

ratings may be available for specific customer requirements,

contact your Caterpillar representative for details. For information

regarding Low Sulfur fuel and Biodiesel capability, please consult

your Cat dealer.