4-14 Edition 47
Engines
Cat Generator Sets
Diesel Ratings
60 Hz
Standby
Prime Continuous
Model
ekW
900 rpm
6CM20C
1037
979
979
8CM20C
1382
1306
1306
9CM20C
1555
1469
1469
3606
2000
1820
1650
3608
2660
2420
2200
3612
4000
3640
3300
3616
5320
4840
4400
720 rpm
3606
1680
1525
1375
6CM25C
1920
1728
1728
3608
2200
2020
1830
8CM25C
2559
2304
2304
9CM25C
2880
2592
2592
3612
3360
3050
2750
3616
4400
4040
3660
12CM32C
6169
5820
5820
16CM32C
8226
7760
7760
600 rpm
6CM32C
2880
2765
2765
8CM32C
3840
3686
3686
9CM32C
4320
4147
4147
514 rpm
6CM43C
6111
5471
5471
7CM43C
7130
6383
6383
8CM43C
8148
7294
7294
9CM43C
9167
8206
8206
12CM43C
12 222
10 942
10 942
16CM43C
16 296
14 589
14 589
NOTE:
All CM engines for land based application rated in accordance with
WBII.
Rating Definitions:
Standby Power Rating
— Output available with varying load for
the duration of the interruption of the normal source power.
Average power output is 70% of the standby power rating.Typical
operation is 200 hours per year, with maximum expected usage
of 500 hours per year.
Prime Power Rating
— Output available with varying load for an
unlimited time. Average power output is 70% of the prime power
rating.Typical peak demand is 100% of prime rated ekW with 10%
overload capability for emergency use for a maximum of 1 hour
in 12. Overload operation cannot exceed 25 hours per year.
Continuous Power Rating
— Output available with non-varying
load for an unlimited time. Average power output is 70-100% of
the continuous power rating. Typical peak demand is 100% of
continuous rated ekW for 100% of operating hours.
Applicable Codes and Standards: AS1359, CSAC22.2 No100-04,
UL142, UL489, UL869, UL2200, NFPA37, NFPA70, NFPA99, NFPA110,
IBC, IEC60034-1, ISO 3046, ISO 8528, NEMAMG 1-22, NEMAMG 1-33,
2006/95/ECforLowVoltage,2006/42/ECforMachinery,2004/108/EC.
Fuel rates
are based on fuel oil of 35° API [16° C
(60° F)
] gravity
having an LHV of 42 780 kJ/kg
(18,390 Btu/lb)
when used at 29° C
(85° F)
and weighing 838.9 g/liter
(7.001 lb/U.S. gal)
. Additional
ratings may be available for specific customer requirements,
contact your Caterpillar representative for details. For information
regarding Low Sulfur fuel and Biodiesel capability, please consult
your Cat dealer.
Cat Generator Sets
●
Diesel Ratings