4-14 Edition 47

Engines

Cat Generator Sets

Diesel Ratings

60 Hz

Standby

Prime Continuous

Model

ekW

900 rpm

6CM20C

1037

979

979

8CM20C

1382

1306

1306

9CM20C

1555

1469

1469

3606

2000

1820

1650

3608

2660

2420

2200

3612

4000

3640

3300

3616

5320

4840

4400

720 rpm

3606

1680

1525

1375

6CM25C

1920

1728

1728

3608

2200

2020

1830

8CM25C

2559

2304

2304

9CM25C

2880

2592

2592

3612

3360

3050

2750

3616

4400

4040

3660

12CM32C

6169

5820

5820

16CM32C

8226

7760

7760

600 rpm

6CM32C

2880

2765

2765

8CM32C

3840

3686

3686

9CM32C

4320

4147

4147

514 rpm

6CM43C

6111

5471

5471

7CM43C

7130

6383

6383

8CM43C

8148

7294

7294

9CM43C

9167

8206

8206

12CM43C

12 222

10 942

10 942

16CM43C

16 296

14 589

14 589

NOTE:

All CM engines for land based application rated in accordance with

WBII.

Rating Definitions:

Standby Power Rating

— Output available with varying load for

the duration of the interruption of the normal source power.

Average power output is 70% of the standby power rating.Typical

operation is 200 hours per year, with maximum expected usage

of 500 hours per year.

Prime Power Rating

— Output available with varying load for an

unlimited time. Average power output is 70% of the prime power

rating.Typical peak demand is 100% of prime rated ekW with 10%

overload capability for emergency use for a maximum of 1 hour

in 12. Overload operation cannot exceed 25 hours per year.

Continuous Power Rating

— Output available with non-varying

load for an unlimited time. Average power output is 70-100% of

the continuous power rating. Typical peak demand is 100% of

continuous rated ekW for 100% of operating hours.

Applicable Codes and Standards: AS1359, CSAC22.2 No100-04,

UL142, UL489, UL869, UL2200, NFPA37, NFPA70, NFPA99, NFPA110,

IBC, IEC60034-1, ISO 3046, ISO 8528, NEMAMG 1-22, NEMAMG 1-33,

2006/95/ECforLowVoltage,2006/42/ECforMachinery,2004/108/EC.

Fuel rates

are based on fuel oil of 35° API [16° C

(60° F)

] gravity

having an LHV of 42 780 kJ/kg

(18,390 Btu/lb)

when used at 29° C

(85° F)

and weighing 838.9 g/liter

(7.001 lb/U.S. gal)

. Additional

ratings may be available for specific customer requirements,

contact your Caterpillar representative for details. For information

regarding Low Sulfur fuel and Biodiesel capability, please consult

your Cat dealer.

Cat Generator Sets

Diesel Ratings