P & I Design Ltd.
Instrument Specification
CLIENT:
REV DATE
BY
CHKD
APPD
CLIENT REF.
Simon Storage
A 30.09.97 MS
DRR
DRR
Fluorobenzene
Tyne Terminal
P & I REF.
SI347014.SPC
SHT
1
OF
2
ITEM:
Electrical
Component
GENERAL
Tag Number
CP3
Service
Fluorobenzene Gantry Control Unit
Area Classification
Zone 1 IIB T4
UNIT
Type
Control Unit c/w Terminals, Indicator Lamps &
Switches
Supply
24V dc
Case
EN Polyester
Connections
1 x M25 & 5 x M20 (Bottom)
Mounting
Surface
Enclosure Class
IP 65
Electrical Classification
EEx de IIC T6
OUTPUT
Type
One Vertical Row of 38 SAK R Terminals.
See Drawing No. SI347025.
1 x Emergency Stop Pushbutton with 1 NO + 1 NC
Contact (GHG 418 8155 R1200)
3 x Momentary Pushbuttons with 1 NO + 1 NC
Contact (GHG 418 8115 R001)
1 x Control Switch in acc. with Circuit
Arrangement A. (GHG 418 8190 R6002)
1 x Yellow 24V dc light
3 x Red 24V dc lights
4 x Green 24V dc lights
OPTIONS
Layout & Label Details
See Drawing No. SI347026.
MANUFACTURERS
Supplier
Parmley Graham Ltd
DATA
Model Number
Ex 48 Control Unit with Built In Components.
DOCUMENTATION
See attached Documentation Specification
ZZ#-ECA1.SPC