P & I Design Ltd.
Instrument Specification
CLIENT:
REV DATE
BY
CHKD
APPD
CLIENT REF.
Simon Storage
A 30.09.97 MS
DRR
DRR
Fluorobenzene
Tyne Terminal
B 23.10.97 PJP
DRR
DRR
P & I REF.
SI347012.SPC
SHT
1
OF
2
ITEM
Isolating Unit
(IS)
GENERAL
Tag Number
XY004
Service
Batch Controller
Area Classification
Zone 1 IIB T4
UNIT
Type
Transformer Isolated
Supply
24V dc
Number of Channels
1
Input
Mechanical Volt Free Contact
Output
Volt Free Changeover Contact
Hazardous Area Limits:
Voltage Max/Min
10.5V / 0
Current Max/Min
13mA / 0
HOUSING
Material
Makrolon
Mounting
DIN Rail
Enclosure Class
General Purpose
Electrical Classification:
Load
EEx ib IIC T4
Unit
[EEx ia] IIC
Electrical Connection
Screw Terminals
OPTIONS
MANUFACTURERS
Supplier
Pepperl & Fuchs
DATA
B
Model Number
KFD2-SR2-Ex1.W
DOCUMENTATION
See Attached Documentation Specification
XY#-ISA2.SPC