P & I Design Ltd.

Instrument Specification

CLIENT:

REV DATE

BY

CHKD

APPD

CLIENT REF.

Simon Storage

A 30.09.97 MS

DRR

DRR

Fluorobenzene

Tyne Terminal

P & I REF.

SI347011.SPC

SHT

1

OF

3

ITEM

Isolating Unit

(IS)

GENERAL

Tag Number

See Sheet 2

Service

See Sheet 2

Area Classification

Zone 1 IIB T4

UNIT

Type

Solenoid Driver

Supply

24V dc

Number of Channels

1

Input

24V dc

Output

24V dc, 35mA

Hazardous Area Limits:

Voltage Max/Min

28V / 0

Current Max/Min

35mA / 0

HOUSING

Material

Makrolon

Mounting

DIN Rail

Enclosure Class

General Purpose

Electrical Classification:

Load

EEx ib IIC T4

Unit

[EEx ia] IIC

Electrical Connection

Screw Terminals

OPTIONS

MANUFACTURERS

Supplier

Pepperl & Fuchs

DATA

Model Number

KFD2-SD-Ex1.48

DOCUMENTATION

See Attached Documentation Specification

XY#-ISA2.SPC