Simon Storage, Fluorobenzene Gantry / Tank 24
Instrument & Electrical Installation Tender Package
DOCUMENT REF: SI347001.INS
ISSUE: B DATE: 13.10.97
PAGE: 7 OF 23
2.7
Clean Up
During and on completion of installation work the Contractor shall remove all surplus
equipment and material and leave areas in a 'brush clean' condition. Refuse shall be
disposed of as directed by the Engineer.
Prior to testing (where damage could arise) and before offering any part of the installation
for acceptance, the Contractor shall clean out all electrical enclosures and wipe down
painted surfaces. If necessary, damage to paintwork shall be made good by touch-up.
Before finally leaving the site, the Contractor shall remove all his accommodation, plant,
tackle and tools of the trade to the satisfaction of the Engineer.
2.8
Earthing
2.8.1
General Soil Conditions
No information is available.
2.8.2
System Earthing
The neutral shall not be regarded as an earth conductor.
In areas where earth rods are to be driven into the ground, it shall be the contractors
responsibility to ensure that there are no other underground services in the immediate
vicinity.
2.8.3
Equipment Earthing
The main earthing bar on the MCC is connected by a separate earth conductor to its main
earth point. All non-live metalwork shall be directly or indirectly bonded to the Main Earth
Bar within the MCC. Such metalworks will include electrical equipment enclosures, motor
frames, tray/ladder rack to be continuously bonded, cable armouring and glands. All glands
which are through clearance holes require an earth tag and connection to the earth system
by 6
sq.mmcable. Care must be taken to ensure that paint, etc. is cleaned away from under
earth connections so that there is good earth continuity.
Direct bonding shall be taken to mean dedicated earth conductors within, or separate from,
plant cable. Separate conductors shall be multi-stranded copper with a green/yellow sheath,
size as specified in the drawings. Indirect bonding shall be taken as earth paths through
armouring.
Note
: (Dedicated earth conductors preferred).
However, a combination of both may be employed, providing that the value of the earth
loop impedance allows flow of fault current sufficient to rupture associated protective
fuses within five (5) seconds.