Previous Page  18 / 56 Next Page
Information
Show Menu
Previous Page 18 / 56 Next Page
Page Background

Dan Jones, acting chief engineer for St. Petersburg, Florida-based Revolution Mo-

tor Industries (RMI), claims that: “Government regulations meant to boost electric

motor efficiency and curb carbon emissions may have started the race for achieving

ever-increasing output with lower energy intakes. But lately it’s the industry itself,

propelled by competition that has developed engines that can not only meet − but

also exceed - the toughest European and U.S. standards”.

******

A

re we barking up the wrong tree? Should we not be looking

at the systems where motors are used? I believe that this is

where the greatest savings are possible – by using a system’s

approach to optimising the motor management. Yes, it is important

to improve efficiency but in general, electric motors are efficient at

rated power and less efficient at low loads. It is therefore important

to use motors more efficiently: This can be done by optimising the

energy consumption under varying loads.

On average motors do not operate at, or consistently at, rate

motor loads. There are a number of reasons for this; these include

the application of compressors, pumps and mechanical presses and

others, where the load could drop considerably − even as low as no

load for a fair period of the operation. Medium range motors are

manufactured in set standard ratings, for example − 37, 45, 55 and

75 kW. So if the load requires a 63 kW peak, a 75 kW motor has to be

installed. On average this means that medium rated motors operate

as low as 50% of rating.

The regulation IEC 60034-30-1 [1] shows the efficiency minimum

requirement to be met to comply with categories IE1 to IE4.

As can be seen in

Figure 1

the improvement in efficiency for mo-

tors above 37 kW is small.

Coverage of IEC 60034-30-1 [1]

Generally speaking three-phase inductionmotors for the intermediate

range 37 kW to 500 kW are relatively efficient when operated at load

close to full rated load.

If we wish to save power the manufacturers would have to

improve efficiency at a load lower than the motor rating − bearing

in mind that many motors do not operate at a constant load peak ef-

ficiency and the Power Factor (PF) should be maintained throughout

the operating range.

In terms of numbers of running motors (installed stock), small

motors are the most common: 2 billion out of an estimated global

total of 2,23 billion are rated at less than 0,75 kW.

The relatively few large motors account for a considerable share

of overall motor electricity consumption. It is estimated that medium

size motors consume almost three-quarters of the global electricity

demand of all motors (Wikström, 2009).

Studies carried out show the approximate world-wide power

consumption admittedly 10 years ago, but I do not believe the trend

has changed radically.

Top-down analysis provides several preliminary results:

• The estimated total global electricity use of all electric motors in

2006 was between 6 900 TWh and 7 200 TWh

• Electric motors account for between 44% and 46% of total global

The author responds to the quote by Dan Jones which suggests that: ‘Competition pushes for innovation ahead of regulations in the electric

motor industry’.

Henry du Preez, Consultant

DRIVES, MOTORS + SWITCHGEAR

Electric Induction Motors:

Power Management System

Figure 1: Efficiency curves for 4 pole induction motors as per IEC

specification IEC 60034-30-1 [1].

Electricity+Control

November ‘16

16