ficient operation. Large machines are generally manufactured to the

specific requirements of the system, whereas the medium range is

manufactured to standard sizes and therefore underutilised and op-

erated at a poor overall efficiency. Mechanical means of control are

inherently inefficient whereas modern power electronics has provided

the advantage of efficient control and operation.

Up to now we have just looked at improving the efficiency of the

ac electric inductionmotor and the use of VFD systems to optimise the

speed for efficient operation. There are recently developed systems

which combine a number of these features to optimise the energy

consumption and lifespan of electrical induction motors. A power

management system combines a number of these features in one

unit which achieves this offering the following in one competitive unit:

• Soft start

• Speed control (VFD)

• Monitoring of the load and adjusting the input voltage to the

motor to optimise the performance of the motor

The first two are generally known and will not be discussed further.

The third requires a few pointers:

• We are aware that the torque produced by an induction motor is

proportional to the square of the input voltage

• The medium range of a motor very seldom runs at or close to

the full rated load; so if we reduce the voltage input to the mo-

tor, maintaining the rated or set speed to maintain the required

torque, there is a large potential to save power

• If the voltage supply to the motor is reduced, the torque decreases

proportionally to the square of the voltage, power is monitored

and the voltage controlled to supply sufficient torque; the loss in

the motor decreases as a result of reduced current. Iron losses are

less due to reduced voltage and current is down due to reduced

load, the PF being maintained at the higher value.

• Because the system is fully automated when the motor load drops

for any reason, the voltage will be reduced and controlled to take

advantage of the lower load condition. If the load increases, volt-

age is automatically restored

Conclusion

South Africa’s generation capacity is stated to be 44 175 MW; if the

usage is taken as 75%, the usage would be 33 131 MW, assuming that

the electric motor's load is 60% which amounts to 19 878 MW (based

on figures quoted in various studies). From the studies as quoted in

[2] if we assume that 67% of power is used in medium range motors,

this would amount to 13 318 MW.

Making the assumption that 50% of the medium range motors

operate on a fluctuating load and only 50% of these are suitable for

a power management system with a potential saving of 20%, the

capacity saved would be approximately 670 MW − equivalent to one

large generator set at one of the newer power stations.

Currently there is a unit available that is a ‘Power Management Sys-

tem’ which optimises the energy consumption and lifespan of electric

induction motors. The unit is a high quality motor management unit

which provides the following:

• Soft start

• Controlled shutdown

• Automatic shutdown

• Energy reduction to optimise power savings

VFD speed control for the optimal matching of the speed to best suit

the driven equipment:

• Further advantages are its lifespan optimisation because of:

• Reduction in operating vibration

• Reduction in operating temperature

• Motor overload and thermal protection

• Reduction in stresses in the winding due to ramp-up and ramp-

down operation

• Reduction in temperature due to effectively controlling power

requirement (efficiency and PF)

The system's approach would be the only effective solution to power

saving. A management system that optimises the energy consump-

tion use by the motor would be the best way to achieve maximum

system efficiency and power savings. Alternative power sources

solar, wind etc. should not be discarded but does not save on power

consumption.

References

[1] IEC 60034-30-1:2014. Rotating electrical machines - Part 30-1:

Efficiency classes of line operated ac motors (IE code).

[2] Waide P, Brunner, CU. Energy-efficiency policy opportunities for

electricmotor- driven systems. International EnergyAgency. Page 39

[3] Limiter Power Management System (patent pending).