5/82
Hand Tools
5
Design:
Casing made of impact-resistant plastic. With selectable limit values for ISO
measurement, green LED for test passed, red LED for test/external voltage, switchable probe
tip for triggering the measuring process, internal memory, voltage measurement with low-
pass filter, automatic discharge of capacitive voltage. Insulation resistance (50 V-1000 V)
with calculation of the resulting current leak, polarisation index (PI) and dielectric absorption
ratio (DAR).
Application:
For insulation and low ohmic measurements on electrical systems, devices,
wires, engines and generators.
Scope of delivery:
Measuring device, switchable probes, measurement lines, crocodile
clamps, rubber case, batteries and bag.
Order No.
0100
Model
IT 101
5586
462.50
Low resistance
0.01 Ohm–40 Ohm
Insulation resistance
1 kOhm–20 GOhm
Resistance
0.01 Ohm–40 kOhm
Voltage
0.1 V–600 V
Measurement value memory
500
Measuring procedure
TRUE RMS
Measurement category
CAT IV 600 V
Dimensions (L x W x H)/weight
207 x 95 x 52 mm/630 g
Batteries
4 x Mignon AA/LR6
(W514)
Insulation and resistance measuring instrument IT 101
IP 40
CAT
IV
Design:
Automatic test procedure with pass/fail indication for Class
I, II (III) and line test. Voltage measurement at external isolated safety
plugs. Three-phase test items tested via optional measuring adapter.
The limit values are preset in line with VDE standard.
Battery
capacity for 2500 test samples. Supplied with carry bag and belt, test
lead with crocodile clip, power cable and batteries.
Application:
For
safety checks (DGUV-Rule-3-tests) of electrical
equipment and work materials according to VDE 0701-0702,
DGUV Rule 3, OVE/ÖNORM E 8701, NEN 3140. Suitable for electrical
engineering, industry, maintenance works, servicing and communities.
Order No.
0710
0725
Model
ST 710
ST 725
5561
456.50
735.00
Protective conductor resistance
0.05–20 Ohm
0.05–20 Ohm
Test current
± 200 mA DC
± 200 mA DC
Insulation resistance
0.1–20 MOhm
0.1–20 MOhm
Test voltage
500 V DC
250 V/500 V
Protective earth/contact cur-
rent via differential measure-
ment/direct measurement
–
0.25–20 mA/0.1–2 mA
Protective earth/contact
current via alternative cur-
rent leakage method
0.1–20 mA
0.25–20 mA
FI/RCD protective
conductor test current
–
30 mA + 150 mA
Performance test
R
PE
, R
ISO
, continuity and short
circuit test of the phase/neutral wire
R
PE
, R
ISO
, continuity and short
circuit test of the phase/neutral wire
Voltage
50–270 V
50–270 V
Dimensions (L x W x H)/weight
270 x 115 x 55 mm/800 g
270 x 115 x 55 mm/950 g
Batteries
6 x Mignon batteries 1.5 V
6 x Mignon AA/LR6
(W511)
ST 710/ST 725 device testers
5561 0710
5561 0725
5561
Battery operated.
Testing of electrical devices/tools
with on/off button, heating devices, power tools, lights,
cable reels, multiple distributors and domestic appliances.
Protective earth/contact current via alternative current
leakage method.
0710
5561
Battery and mains operation.
Testing of devices with
mains voltage-dependent switching elements/power
supply/relay, such as electronically controlled devices/
tools, information and communication technology devices
and equipment that can be fully tested only with mains
voltage.
Protective earth/contact current via differential
measurement/direct measurement.
Data memory
for 999 test objects, read out via micro-USB port. Also
includes integrated real-time clock to store the measured
values with test date, micro USB cable and reading
software (CD).
0725
600 V
Test and measuring devices
956