points. Amore discriminating rule-of-thumb is to stipulate that the SIF response time should be less
than 50% of the value that would otherwise cause the SIF execution timetomatch the PST.
Breaches of this rule are not necessarily hazardous however and a more rigorous analysis of the
systemprovisionsmay well demonstrate that values in excess of 50% are perfectly acceptable.