a CSA International company

FMEA of the (close/open)

Circuit type A

1oo1 EQUATIONS

Parameter name

Symbol Equation / source

Close/Open

without diag

Proof Test Interval [PTI]

T

Given, for this example

2190

Mean Time To Repair

MTTR

Given, for this example

8

Type A/B

type A

Given, for this example

type a

Total failures:

l

From FMEA

5.85E-08

Safe diagnosed failures:

l

SD

From FMEA

0.00E+00

Safe undiagnosed failures:

l

SU

From FMEA

1.05E-08

Dangerous diagnosed failures:

l

DD

From FMEA

0.00E+00

Dangerous undiagnosed failures:

l

DU

or High demand mode, PFH per (hour)

4.80E-08

Safe no-effect failures

l

NE

From FMEA

1.46E-06

Diagnostic coverage:

DC

l

DD

/ (

l

DU

+

l

DD

)

0%

Safe Failure Fraction:

SFF (

l

SD

+

l

SU

+

l

DD

) /

l

18 %

Channel equivalent down time

t

CE

(l

DU

/

l

D

)(T/2 + MTTR) + (

l

DD

/

l

D

) MTTR

1.10E+03

PFD

AVG

(using 61508-6 equation)

PFD

AVG

(l

DU

+

l

DD

) t

CE

5.30E-05

PFD

AVG

(using simplified equation)

PFD

AVG

l

DU

(T / 2+MTTR) + (

l

DD

MTTR)

5.30E-05

PFD

AVG

(using IEC 61508-6,equation) PFD

AVG

1- e

-(

λdd+λdu) tce

5.30E-05

SIL capability (Low demand mode)

SIL 1