Local Fuel – Shoreham Oil Terminal

Gasoline Ship Import – Layers of Protection Analysis

P & I Design Ltd

DOCUMENT NO: LF364002_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: E DATE: 30.07.15

Tel: + 44 (0)1642 617444

PAGE 30 OF 38

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

Other causes not assessed in detail as their contribution is significantly lower than causes 1

through 3.

Cause

Description

Notes

4

Valve failure (or

passing) on a route

where import is not

expected.

All routing will have at least two isolation valves.

Probability of this failure leading to an overfill is very

low compared to other initiating events.

5

Changes in the filling

rate due to changing

operations on other

tanks.

Not considered as an issue, as only one tank is filled at a

time. The maximum quoted rate for an import is

400m

3

/hr

6

Failure to terminate

filling at the ship on

request from terminal

The ship operators and Local Fuel operations are

monitoring the transfer and will normally stop at the

required parcel quantity. Contact is made with the ship

operations to warn that the site is reaching its required

quantity. It is not possible that part loads will be

transferred.