18

How did we solve the problem?

§

For example,

§

A proportion of the

λ

DU

were related to the device being out of calibration

§

Not going to do a full calibration before each delivery

§

Terminal receives product from different suppliers

§

Uses accurate, calibrated flow meters in-line

§

Twice a month, levels are compared to metered flow

§

This meets some of the requirements of a calibration

§

A part of the

λ

DU

relating to calibration can be moved to

λ

DD

©ABBGroup

October23,2016|Slide35

©ABBGroup

October23,2016|Slide36

Summary - 1

§

Specialist Inspector was correct in rejecting the SIL claim

§

It wasn’t a ‘good’ certificate

§

IEC61511 Ed 2 probably wouldn’t change the decision

§

Manufacturers have practical difficulties in claiming Prior Use

§

Data relating to the each revision of the product

§

Site or operating environment specific affects

§

Really disappointing that certification bodies issue certificates like this