15

Was the Inspector correct?

©ABBGroup

October23,2016|Slide29

§

Looking at the evidence on the certificate and report

§

Yes

§

It’s really disappointing to see certification bodies issuing

certificates quoting end-user concepts

§

This was a ‘bad’ certificate

§

End user and design contractor thought they had

bough a SIL 2 solution

§

They wanted their money back

©ABBGroup

October23,2016|Slide30

Would IEC61511 Ed 2 change the decision?

§

Only one table in Ed 2

§

Seems to make HFT for SIL 2 easier

§

‘Flips’ the logic of Ed 1

IEC 61511-1 Ed 2 Table 3 – Minimum HFT requirements according to SIL

SIL

Minimum required HFT

1 (any mode)

0

2 (low demand mode)

0

2 (continuous mode)

1

3 (high demand or continuous mode)

1

4 (any mode)

2