Table of Contents Table of Contents
Previous Page  579 / 1143 Next Page
Information
Show Menu
Previous Page 579 / 1143 Next Page
Page Background

10

©ABBGroup

October23,2016|Slide19

Two Types of Instruments in BS EN 61508-2 Ed 2

§

BS EN 61508 has two tables relating to hardware

fault tolerance

§

Used by the manufacturers to demonstrate

benefits of improvements in technology

§

Type A instruments – simple instruments

where all failure modes can be predicted

§

Type B – complex, usually programmable

instruments incorporating intelligence

§

The Radar Level transmitter was a Type B

instrument

©ABBGroup

October23,2016|Slide20

BS EN 61508-2 Ed 2 HFT Type B Component

§

Need at least 90% SFF to reduce HFT to 0 for SIL 2

§

Used by many manufacturers on certificates

Subsystem with Type B Components

Safe failure fraction

Hardware fault tolerance (see note 1)

0

1

2

< 60 %

not allowed

SIL1

SIL2

60 % - < 90 %

SIL1

SIL2

SIL3

90 % - < 99 %

SIL2

SIL3

SIL4

≥ 99 %

SIL3

SIL4

SIL4

BS EN 61508-2 Ed 2 Table 3