7

©ABBGroup

October23,2016|Slide13

Hardware Fault Tolerance using BS EN 61511-1 Ed 1

BS EN 61511-1 Ed 1 Table 6

SIL 2 Logic

Solver

SOV Trip Valve

Level

SIL

Minimum hardware fault tolerance for sensors, non-

programmable logic solvers and final elements

1

0

2

1

3

2

4

Special requirements apply (see BS EN 61508)

Hardware Fault Tolerance using BS EN 61511-1 Ed 1

§

This shows for target SIL 2, a HFT of 1 is required

§

This means two sensors are required

§

This is the traditional method of dealing with high levels

of risk reduction