What was the problem?

§

Manufacturers certificate and FMEDA report stated that the

device was: -

§

Type B

§

SIL 2 with HFT = 0

§

In the FMEDA report a table of failure rates show

§

SFF = 81%

§

But BS EN 61508 Ed 2 shows that for Type B, SFF>90% is

required for SIL 2, HFT 0

©ABBGroup

October23,2016|Slide23

How can they claim SIL 2 with HFT 0?

§

FMEDA report states

§

Radar Transmitters meet requirements of IEC61511

11.4.4 Prior Use

§

Justified by detailing data from field tracking database

and 100,000,000 hours

§

Report and justification was sent to the HSE Specialist

Inspector for consideration

©ABBGroup

October23,2016|Slide24