Table of Contents Table of Contents
Previous Page  575 / 1143 Next Page
Information
Show Menu
Previous Page 575 / 1143 Next Page
Page Background

6

©ABBGroup

October23,2016|Slide11

Three Criteria for a SIL Compliant Design

§

The Control/ Instrument / Electrical engineer has to demonstrate three

criteria are met for a compliant SIF design:

1.

Control of Random Hardware Failures – these are the PFDavg

calculations

2.

Meet Architectural Constraints – Hardware Fault Tolerance

3.

Control of Systematic Faults

§

The issue with the certificate seemed to be related to claims for

Hardware Fault Tolerance (HFT)

©ABBGroup

October23,2016|Slide12

Ways to Address Hardware Fault Tolerance

§

BS EN 61511-1 Ed 1 Tables 5 and 6

§

BS EN 61508-2 Ed 2 Route 1

H

- Type A/ Type B and Safe

Failure Fractions

§

BS EN 61511-1 Ed 1 Prior Use

§

BS EN 61508-2 Ed 2 Route 2

H