The SIL 2 Safety Instrumented Function

§

Hazard study identified a scenario where overfill of storage tanker would lead to a

Vapour Cloud Explosion

§

A Buncefield type event

§

Layer of Protection Analysis (LOPA) identified SIL 2 overfill protection required

©ABBGroup

October23,2016|Slide7

SIL 2 Certified Level Sensor

§

Design contractor installed a

single SIL 2 Certified Radar

Level sensor to detect the high

high level and close an in-line

shut off valve

§

Level sensor certified as SIL 2,

HFT 0, Type B

§

Implies a single sensor can

be used for SIL 2

requirement

©ABBGroup

October23,2016|Slide8

E-1