Simon Storage - ISCo East
No.7 Switchroom – Existing Board (AC) Transition to new MCC(s)
P & I Design Ltd
DOCUMENT NO: SI451003_INS
2 Reed Street, Thornaby, UK, TS17 7AF
ISSUE: A DATE: 22.02.13
Tel: + 44 (0)1642 617444
PAGE 8 OF 16
Fax: + 44 (0)1642 616447
www.pidesign.co.uk4.4
Cabling (Ex Board AC)
The following drives are to be relocated to the new MCC 2
P3-8
P3-9
P3-14
C3-32
4.4.1
P3-8
Existing ISCo Drg. Ref.
SPW-95-214 Rev. 1
New P&I Design Drg. Ref.
SI451060_DWG Rev A
Control cabling as listed below to be pulled back from existing board and
terminated to MCC 2 as shown on P&I Drg.
C30315
C30316
C30317
Drive cable to be replaced as shown on cable schedule.
Cables that will become redundant to be isolated and removed
P30313 (Power supply to starter panel)
C30318 (Crash stop panel)
4.4.2
P3-9
Existing ISCo Drg. Ref.
SPW-95-215 Rev. 1
New P&I Design Drg. Ref.
SI451061_DWG Rev A
Control cabling as listed below to be pulled back from existing board and
terminated to MCC 2 as shown on P&I Drg.
C30325
C30326
C30327
Drive cable to be replaced as shown on cable schedule.
Cables that will become redundant to be isolated and removed
P30323 (Power supply to starter panel)
C30328 (Crash stop panel)