No.7 Switchroom – Existing Board (AC) Transition to new MCC(s)
P & I Design Ltd
DOCUMENT NO: SI451003_INS
2 Reed Street, Thornaby, UK, TS17 7AF
ISSUE: A DATE: 22.02.13
Tel: + 44 (0)1642 617444
PAGE 9 OF 16
Fax: + 44 (0)1642 616447
www.pidesign.co.uk4.4.3
P3-14
Existing ISCo Drg. Ref.
SPW-07-796 Rev. 1
New P&I Design Drg. Ref.
SI451065_DWG Rev A
Control cabling as listed below to be pulled back from existing board and
terminated to MCC 2 as shown on P&I Drg.
C30642
Drive cable to be pulled back from existing board and terminated to MCC 2 as
shown on P&I Drg.
Cables that will become redundant to be isolated and removed
P30640 (Power supply to starter panel)
C30644 (Crash stop panel)
4.4.4
C3-32
Existing ISCo Drg. Ref.
n/a
New P&I Design Drg. Ref.
n/a
Drive cable to be replaced as shown on cable schedule.