INTRODUCTION
This document details the scope of work required to upgrade the Tank 24 road loading
facility at Simon Storage Tyne Terminal.
The flowmeter and batcher are to be replaced with different units with the batching valve
also being replaced but on a like for like basis. Modification will be required to both the
batcher logic wiring and the pneumatic supply to the control valve.
The works are limited in scope so only the affected drawings are included in this scope of
work. The finished installation shall comply with drawings included in the appendices, the
existing drawings are included for reference.
3
SCOPE OF WORK
The scope of work is as detailed in the following sections and as shown on the
documentation listed below.
Ensure the system is isolated both pneumatically and electrically before commencing any
work.
3.1
Scope of Work – Flowmeter
The existing V-cone meter is to be removed and replaced with a turbine meter.
The works comprise, briefly :-
De-gland cable FM3/JB27 at both the meter and the I.S. junction box FJB27 and
remove the cable.
The existing V-cone meter will be removed from the pipeline and replaced with the
turbine meter by others. The turbine meter has a 12m. flying lead. The flying lead is
to be glanded and terminated directly to the replacement batcher FM3. If the flying
lead is not sufficiently long an intermediate junction box suitable for I.S. circuits
shall be used.
3.2
Scope of Work – Batcher
The existing Schillings batcher is to be removed and replaced with a new Fluidwell
batcher.
The works comprise, briefly :-
De-gland cable IP1/FM3 at both the batcher and the pneumatic panel and remove
the cable, plugging vacated cable entry at pneumatic panel.
De-gland cable FJB27/FM3 from the Schillings batcher.
Remove the existing batcher and mount the new Fluidwell batcher.
Re-terminate cable FJB27/FM3 in the new batcher as shown on drawing
SI347012_DWG Rev.B
Terminate the flying lead cable from the new turbine meter in the batcher as shown
on drawing SI347012_DWG Rev.B