Inter Terminals Ltd. - Tyne Terminal
Tank 24 Road Loading Overspill System – I.S. Calculation
P & I Design Ltd
DOCUMENT NO: 16115CAL001
2 Reed Street, Thornaby, UK, TS17 7AF
ISSUE: A
Tel: + 44 (0) 1642 617444
DATE: 02/02/17
Fax: + 44 (0) 1642 616447
PAGE: Page 6 of 8
www.pidesign.co.uk3.2
Capacitive Sensor
Manufacturer: Pepperl+Fuchs
Model: CJ4-12GK-N
Certification: ExII 1G EEx ia IIC T6
Certificate No.: TÜV 03 ATEX 2003 X
Supplement 2 to the ATEX Certificate confirms that this model of sensor falls into
Category 1.
This sensor cannot be classified as Type 1 from the ATEX Certificate as the power supplied
by the isolator (45mW) is higher than the input power for Type 1 (34mW). Type 2 satisfies
input voltage, current and power considerations while giving a very conservative ambient
temperature limit of 49°C to achieve T6.
The data collected from the ATEX Certificate for use in 16115CAL002 and 16115CAL003
has been highlighted below:
Table 1: A Table from ATEX Certificate TÜV 03 ATEX 2003 X. Yellow Highlighting shows data used.
The data collected from the sensor’s datasheet for use in 16115CAL002 and 16115CAL003
is shown below:
Figure 2: Selected data from CJ4-12GK-N datasheet.