Conoco Phillips – Bramhall Terminal

Gasoline Safety Instrument System - Functional Safety Assessment

P & I Design Ltd

DOCUMENT NO: SI297020_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: C DATE: 30.03.17

Tel: + 44 (0)1642 617444

PAGE 9 OF 21

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

Common cause failures are not specifically considered in the SRS. However, for a 1oo1

configuration, common cause failures are not normally an issue.

Document SI297013_RPT, Section 4, details the safe state of the process for each SIF. The

system is designed such that all components are energise to operate and the safe states is de-

energised with flow to all the tanks isolated.

There are not considered to be any

individually safe process states which, when occurring

concurrently create a separate hazard.

The sources of demand were detailed in the LOPA referenced in section 4.1 and the SIF shall

operate as a low demand mode system with demands placed on the system from operations no

more frequently than once every two years. Ref: Document SI297013_RPT, section 2.

Document SI297013_RPT, Section 4, details the annual proof test interval.

Document SI297013_RPT, Section 4, details the response times.

The SIF shall operate as a low demand mode system.

Ref: Document SI297013_RPT, section 2.