Gasoline Safety Instrument System - Functional Safety Assessment

P & I Design Ltd

DOCUMENT NO: SI297020_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: C DATE: 30.03.17

Tel: + 44 (0)1642 617444

PAGE 12 OF 21

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

Document SI297013_RPT, section 2 details the MTTR.

No dangerous combinations of output states of the SIS have been identified.

Document SI297013_RPT, section 2 states: This system will be installed in mainland UK

where it will not be subjected to extremes of temperature or humidity. The individual

elements of the system shall be designed for the process and operating conditions, the

environment and the site electrical area classification. Specifically, all wetted parts should be

suitable for Petroleum Spirits and Distillates (Gasoline, Diesel, Kerosene etc.).

The terminal operates in a single mode. The operation of the terminal is essentially a batch

process with parcels of fuel being imported to the terminal. The SIS is in operation at all times

unless the logic panel is de-energised. In which case the pipeline isolation valve would be

closed.

Document SI297013_RPT, section 2, states that isolation valves must conform fire safe

requirements.