4-14
Chapter 4
– Air Conditioner Components
Go to Chapter Start-
Table of Contents-
IndexThe valve opens and closes depending on system need for refrigerant at
the inlet to the evaporator. Figure 4-10 shows an internally equalized
valve.
Note:
Insulating material is wrapped around the expansion
valve, and coil or bulb where it attaches to the evapo-
rator outlet. This is done to improve heat energy
conduction and prevent condensation forming on the
valve.
2. Expansion Tubes
Expansion tubes are also called fixed orifice tubes. They are used in some
systems, always in combination with an accumulator instead of a re-
ceiver-drier. The tubes have no moving parts and are not adjustable.
When used, an expansion tube is located inside the inlet tube of the
evaporator. It restricts but allows a continuous flow of refrigerant to the
evaporator coil.
An expansion tube is shown in Figure 4-11. When an expansion tube is
used in place of a valve, liquid refrigerant may pass through the evapora-
tor before it can change to a gas. The accumulator prevents liquid refriger-
ant from reaching the compressor. When an expansion tube is defective it
must be replaced using a special tool.
O-RING
EXPANSION TUBES FIT INSIDE
THE EVAPORATOR INLET FITTING
ORIFICE TUBE
INTERNALLY EQUALIZED VALVE
PRESSURE
OUTLET
PRESSURE
FROM
CAPILLARY
Figure 4-10
The internally equalized
TXV is shown. This valve is
designed with either tem-
perature sensing coils or
bulbs at the end of its capil-
lary tubes.
Figure 4-11
The expansion (fixed orifice)
tube is used in place of an
expansion valve. There are
no moving parts.