Transmitter Wiring - TS Types
The typical wiring for the
TS
series transmitters is shown below. The system would include a transmitter,
power supply and digital instrument. If you have any difficulties with setting up your transmitter, our sales engi-
neers are available to provide technical support.
RTDs may have different color coding than our standard Black, Black, Red, and Red. As a general rule, for 3
wire RTDs, connect two of the like colors to terminal #1 and #2 and one of the second colors to terminal #3 (The
remaining wire can be cut off or taped back). For 4 wire RTDs, connect the second two like color wires to termi-
nals #3 and #4. To connect the transmitter to your instrument and power supply, use our part number
20I02-PP-S
(see page 169) and attach the instrument wire on terminals #5 and #6.
Note:
When wiring your transmitter the
NEGATIVE
wire of a thermocouple is always coded
RED.
Thermocouple
Hookup - TS
2 Thermocouple
Positive
4 Not used
PC
Connection
(Factory use)
5 Not used
3 Not used
1 Thermocouple
Negative
Instrument
Input
+
-
Power
Supply
Output
8.0 - 36 VDC
+
-
6
7
Factory Configured Non - Isolated
3 Wire RTDs use terminals 1, 2, & 3
4 wire RTDS use terminals 1, 2, 3, & 4
Power Supply 8.0 - 36 VDC
Ambient temperature range:
-40 to +185°F
DIN head mount
Size 1.75” Diameter x 1.08” tall
Permissible R Load =
Supply Voltage (VDC) -8/0.022
2 RTD - Black wire
(common)
4 RTD - Red wire
4 wire RTD
Hookup - TS
PC
Connection
(Factory use)
5 Not used
3 RTD - Red wire
1 RTD - Black wire
(common)
7
Power
Supply
Output
8.0 - 36 VDC
+
-
Instrument
Input
+
-
6
Factory Configured Non - Isolated
Thermocouples:
B, C (AE), E, J, K, N, R, S, T
Thermocouples use terminals 1 & 2
Power Supply 8.0 - 36 VDC
Ambient temperature range:
-40 to +185°F
DIN head mount
Size 1.75” Diameter x 1.08” tall
Permissible R Load =
Supply Voltage (VDC) -8/0.022
Transmitters - In Head Style, Wiring - Non-Isolated Transmitter - TS
Page 170