Previous Page  171 / 204 Next Page
Information
Show Menu
Previous Page 171 / 204 Next Page
Page Background

1 2 3 4

Output

R

Load

+ -

Thermocouple

1 2 3 4

RTD

(3 wire)

1 2 3 4

Power

Supply

5 6

+ I

R

Load

Power

Supply

Transmitter Wiring - TSI Types

The typical wiring for the

TSI

series transmitters is shown below. The system would include a transmitter,

power supply and digital instrument. If you have any difficulties with setting up your transmitter, our sales

engineers are available to provide technical support.

RTDs may have different color coding than our standard Black, Black, Red, and Red. As a general rule, for 3

wire RTDs, connect two of the like colors to terminal #1 and #2 and one of the second colors to terminal #3 (The

remaining wire can be cut off or taped back). For 4 wire RTDs, connect the second two like color wires to

terminals #3 and #4. To connect the transmitter to your instrument and power supply, use our part number

20I02-PP-S

(see page 169) and attach the instrument wire on terminals #5 and #6.

Note:

When wiring your transmitter the

NEGATIVE

wire of a thermocouple is always coded

RED.

2 RTD - Black wire

(Common)

1 RTD - Black wire

(Common)

3 RTD - Red wire

RTD Hookup -TSI

PC

Connection

(Factory use)

4 RTD - Red wire

Instrument

Input

+

-

Power

Supply

Output

8.0 - 36 VDC

+

-

2 Thermocouple

Positive

1 Thermocouple

Negative - Red

Thermocouple Hookup -TSI

PC

Connection

(Factory use)

Instrument

Input

+

-

Power

Supply

Output

8.0 - 36 VDC

+

-

Transmitters - In Head Style, Wiring - Isolated Transmitter - TSI

Manufacturing, Engineering and Sales Since 1938

Phone: 617.527.4385 Fax: 617.964.3746 Email:

sales@asrichards.com

TS

Hookup

Page 171

Visit our website at