ASR900HY - 1/4 DIN Panel Mount
Item
General Specifications
Power supply
100-240 VAC, 50-60 Hz
Power Consumption
10 VA max.
Display Accuracy
±0.5% of FS ±1 Digit, thermocouple (B, E, J, K, L,
R, S, T, U, W, PL2)
±01.0% of FS ±1 Digit, thermocouple (N)
±0.5% of FS ±1 Digit, RTD (KPt100Ώ, Pt100Ώ)
Sampling Time
250 ms
Relay:
Contact capacity: 1C, 240V AC, 3 A,
30V DC, 3A (resistive load)
Control Output
SSR:
More than approx. 12V DC (Min 600Ώ
resistive load), with disconnection, limit within
approx. 30 mA, Time resolving power: smaller
one between 0.1% and 10 ms
SCR:
4 - 20 mA DC (resistive load less than 600Ώ)
Accuracy: ±0.5% of FS (range 4 - 20 mA DC)
resolving power : approx. 3,000
Dielectric strength
2,300 V AC, 50 / 60 Hz, for 1 min (1st terminal -
2nd terminal - between the earth terminal)
1,500 V AC, 50 / 60 Hz, for 1 min (2nd terminal -
between the F.G)
Insulation Resistance
Min 20 MΏ (500V DC), 1st terminal -
2nd terminal - between the earth terminal
Ambient temperature
0 to 50°C
Storage Temperature
-25 ~ 65°C
Ambient Humidity
Range
35 ~85 % RH (without dew condensation)
Net Weight
Approximately 472 grams
Panel Cut-out
92.0 mm x 92.0 mm (3.62” x 3.62”)
Instrument Outline
96 mm x 96 mm x 112.5 mm (3.78” x 3.78” x 4.43”)
Allowable wiring
resistance
RTD (max 10Ώ, however resistance among 3 wires
should be same)
Cold junction
compensation error
±1.5°C (15 ~ 35°C), ±2.0°C (0 ~ 50°C)
Input signal
break detection
OFF, UP/DOWN Scale selection (Thermocouple),
UP Scale (RTD)
The Richards model
ASR900HY
micro processor temperature process controller is a very economical solution for temperature control in
your process. These instruments are also inexpensive enough that they can also be used in situations where just an indicator is required.
They are accurate and have selectable inputs for all standard thermocouple Types (B, C, E, J, K, N, R, S, T, & Platinel II) and Pt100Ώ &
KPt100Ώ three wire RTDs. Their sizes are excellent for panel mounting of multiple instruments. The
ASR900HY
is a bezel mount instrument,
which require no mounting screws for installation in panels.
Features:
√
Fuzzy Function, PID auto tuning
√
Control Outputs: Relay, SSR, & SCR
√
RS485/422 communication function
Example range: Type K (Thermocouple): -200 to 1370°C (0 to 2498°F
)
Digital Temperature Controller - ASR900HY
Manufacturing, Engineering and Sales Since 1938
Phone: 617.527.4385 Fax: 617.964.3746 Email:
sales@asrichards.comASR900
Page 175
Visit our website at
www.asrichards.comASR900HY
1
Instrument Rear Panel - Hookups
Thermocouple
18
19
20
TC
Red
~
2
mV / V
4
5
6
7
OUT1
OUT1
SSR / SCR
RET
OUT2
SSR / SCR
RET
Power
1
3
8
9
10
11
12
13
14
15
16
17
18
19
20
/
VVVV\
A
B
B
RTD