5/79

Articles marked ◊ are not held in stock, procurement is effected at short notice.

5

Hand Tools

Design:

Casing made of impact-resistant plastic. With selectable limit values for ISO

measurement, green LED for test passed, red LED for test/external voltage, switchable

probe tip for triggering the measuring process, internal memory, voltage measurement with

low-pass filter, automatic discharge of capacitive voltage. Insulation resistance (50 V–1000 V)

with calculation of the resulting current leak, polarisation index (PI) and dialectric absorption

ratio (DAR).

Application:

For insulation and low resistance measurements on electrical installations,

equipment, cables, motors and generators.

Scope of delivery:

Measuring device, switchable probes, measurement lines, crocodile clamps,

Order No.

0100

Model

IT 101

5586

445.20

Low resistance

0.01 Ohm–40 Ohm

Insulation resistance

1 kOhm–20 GOhm

Resistance

0.01 Ohm–40 kOhm

Voltage

0.1 V–600 V

Measured data storage

500

Measuring procedure

TRUE RMS

Measurement category

CAT IV 600 V

Dimensions (L x W x H)/weight

207 x 95 x 52 mm/630 g

Batteries

4 x Mignon AA/LR6

(514)

Insulation and resistance measuring instrument IT 101

IP 40 CAT

IV

Design:

Automatic test procedure with pass/fail indication for Class I, II (III), and line test.

Voltage measurement at external isolated safety plugs. Three-phase test items tested via

optional measuring adapter.

The limit values are preset in line with VDE standard.

Battery

capacity for 2500 test items. Supplied with carry bag and belt, test lead with crocodile clip,

power cable and batteries.

Application:

For

safety checks (DGUV-Rule-3-tests) of electrical equipment and work

materials according to VDE 0701-0702,

DGUV Rule 3, OVE/ÖNORM E 8701, NEN 3140.

Suitable for electrical engineering, industry, maintenance works, servicing and communities.

Order No.

0710

0725

Model

ST 710

ST 725

5561

445.40

699.70

Protective conductor resistance

0.05 Ohm–20 Ohm

0.05 Ohm–20 Ohm

Test current

± 200 mA DC

± 200 mA DC

Insulation resistance

0.1 MOhm–20 MOhm

0.1 MOhm–20 MOhm

Test voltage

500 V DC

250 V/500 V

Protective earth/contact cur-

rent via differential measure-

ment/direct measurement

0.25 mA–20 mA/0.1 mA–2 mA

Protective earth/contact current via

alternative current leakage method

0.1 mA–20 mA

0.25 mA–20 mA

FI/RCD protective conductor test current

30 mA

Performance test

R

PE

, R

ISO

, continuity and short

circuit test of the phase/

neutral wire

R

PE

, R

ISO

, continuity and short

circuit test of the phase/

neutral wire

Voltage.

50 V–270 V

50 V–270 V

Dimensions (L x W x H)/weight

270 x 115 x 55 mm/800 g

270 x 115 x 55 mm/950 g

Batteries

6 x Mignon batteries 1.5 V

6 x Mignon AA/LR6

(511)

ST 710/ST 725 device testers

5561 0710

5561 0725

5561

Battery operated.

Testing of electrical devices/tools with on/off button,

heating devices, power tools, lights, cable reels, multiple distributors and

domestic appliances.

0710

5561

Battery and mains powered.

Testing of devices with mains voltage-dependent

switching elements/power supply/relay, such as electronically controlled devices/

tools, information and communication technology devices and equipment that

can be fully tested only with mains voltage. Data memory for 999 test objects,

read out via micro-USB port. In addition, includes integrated real-time clock

to store the measured values with test date, micro USB cable and reading

software (CD).